Online power protection for rack equipment
The APC Easy UPS On-Line SRV6KRIRK provides 6000 VA / 6000 W of power capacity for compatible servers, storage systems, network equipment and other business loads. Its online double-conversion topology and pure-sine output support equipment that needs a regulated power supply. Select connected equipment by its combined wattage and VA demand, allowing for startup loads and future expansion.
The rack-mounted system combines a UPS power module and a separate included battery enclosure, occupying 4U in total. The front LCD and LED indicators show operating information locally, while audible alarms report battery operation, low battery and overload conditions. Internal automatic and manual bypass supports the UPS operating modes.
Hardwired connection and monitoring
Both the input and output use single-phase three-wire hardwired connections: phase, neutral and protective earth. Plan the electrical circuit, cable routing and downstream power distribution before installation. All electrical work must be performed by a qualified electrician in accordance with the installation manual and applicable electrical codes, including the specified external backfeed protection.
USB Type B, RS-232 and an Intelligent Slot provide management connection options. Network management requires a suitable optional card; no cloud subscription or software entitlement is promised with this listing. Emergency Power Off terminals support an appropriate site safety arrangement.
Technical specifications
| Exact model | SRV6KRIRK |
|---|---|
| Rated capacity | 6000 VA / 6000 W |
| Topology / waveform | Online double conversion / pure sine wave |
| Nominal voltage | 230 V; output configurable to 220 / 230 / 240 V |
| Input range | 176–300 V at full load; 110–300 V at 60% load |
| Input frequency | 40–70 Hz, auto-sensing |
| Input / output | 1 hardwired 1P+N+E connection each |
| Battery | Included external VRLA lead-acid pack, 192 V; 16 × 12 V 7 Ah |
| Battery pack reference | SRV192RBP-7A |
| Typical recharge | About 4 hours to 90% capacity |
| Rack space | 4U total, two enclosures |
| Dimensions (W × H × D) | 438 × 173 × 710 mm, total system |
| Net weight | 61 kg |
| Operating temperature / protection | 0–40 °C / IP20 |
| Supplier warranty | 12 months |
Battery, installation kit and practical limits
The standard manufacturer bundle includes the external battery pack and rack-mount rails. Check rack depth, usable space and load capacity against the complete 61 kg system. The sealed VRLA battery pack supplies backup power during mains interruptions and requires periodic condition checks and eventual replacement.
Actual backup time depends on connected load, battery charge, age, temperature and operating conditions. A capacity rating alone does not guarantee a fixed number of minutes. Installation services and site electrical components should be planned separately; the supplier warranty stated for this item is 12 months.